A structured inspection checklist for fire doors in non-domestic premises and multi-occupied residential buildings. Based on BS 8214:2016 and BS 9999:2017. For use by competent fire door inspectors.
Door leaf: no holes, damage, or unauthorised modifications
BS 8214:2016
Self-closing device: door closes fully and latches every time
BS 8214:2016, Clause 8.3
Intumescent seals: present, continuous, and undamaged around full perimeter
BS 8214:2016, Clause 8.2
Perimeter gaps: ≤3–4mm on sides and top, ≤8mm at threshold
BS 8214:2016, Table 1
Hinges: minimum three, no missing screws, no excessive movement
BS 8214:2016, Clause 8.4
Glazing: fire-rated glass, seals intact, no cracks or damage
BS 8214:2016, Clause 8.5
Hardware: all ironmongery is fire-rated and correctly fitted
BS 8214:2016
Signage: correct "Fire Door" sign displayed and legible
BS 9999:2017
Certification / test evidence: door set has traceable fire-test evidence
BS 8214:2016